Corrugated stainless steel tubing

Corrugated stainless steel tubing (CSST) include two types. One type is stainless steel tubing be formed with corrugate shape on outside surface. Make it higher efficiency of heat transfer,can be used to connect the form of tube soft and flexible, with good defensive displacement and vibration and noise reduction, mainly used on heat ex-changers. Other type is a type of conduit used for fuel gas distribution in buildings. It has a flexible corrugated stainless steel inner layer and an outer yellow or black plastic jacket. Yellow-jacketed CSST was developed first and is the most common. It has a non-conductive plastic yellow jacket. Black-jacketed CSST is relatively new. Its black jacket is electrically conductive. Manufacturer information indicates this conductive jacket dissipates the energy of indirect lightning strikes that might otherwise pierce or damage the yellow-jacketed CSST.

CSST is not FAC (Flexible Appliance Connector) tubing. Presently, CSST and FAC tubing both use corrugated stainless steel tubing. In the past, FAC used corrugated brass tubing. However, FAC tubing is made only in lengths of 1 to 6 feet, FAC tubing is made with connectors on each end, and FAC tubing does not have a plastic sheath. On FAC tubing the corrugations are visible. CSST’s plastic sheath covers its corrugations.

CSST is used as an alternative to the older standard “black iron” (steel) gas pipe. The inner stainless steel layer of typical residential CSST is .2 to .3 mm thick while the wall thickness of typical residential “black iron” gas pipe is 3 to 4 mm thick. CSST is more expensive than “black iron” gas pipe. However, CSST requires fewer joints, may be safer during earthquakes, and may be easier to install.

CSST is alleged to have an increased risk for lightning related fires. Some believe that CSST is more likely to be pierced by lightning than “black iron” pipe. There are varied opinions over CSST’s fire risk and it has been involved in litigation.

Buildings with CSST should be inspected by experts (licensed plumbers and electricians) to verify proper bonding and installation. The CSST experts should be qualified to assure compliance with the requirements of the manufacturer and local codes. Be aware that most home inspections are not done by licensed plumbers and electricians. Building owners are advised to assure that their CSST system complies with their insurance company’s requirements.

To reduce the possibility of CSST lightning damage: 1) Yellow-jacketed CSST should be bonded (connected to the electrical service panel’s ground bus) at its entrance into a building. Many local codes require this. 2) All CSST should be installed away from metal objects such as metal duct work, metal pipes, electrical wiring, metal beams, or metal conduit.

According to one manufacturer of black-jacketed CSST, their black-jacketed CSST is like “black iron” gas pipe in that it does not need to be bonded at its entrance into a building. They state that their black-jacketed CSST, like “black iron” gas pipe, can be bonded at another location, such as at a bonded metal furnace cabinet. However, be aware that local codes may require bonding at the CSST entrance with all types of CSST.

CSST should not make contact with sharp objects or edges to reduce the possibility of leaks caused by piercing. For example, it should not be installed where things such as picture hanger nails or drywall screws might pierce it,

Some applicable codes:

NFPA (National Fire Protection Association) 70, 2014 Edition, (NEC 2014), 2014 Edition Section 250.104, Bonding of Piping Systems and Exposed Structural Metal.

NFPA (National Fire Protection Association) 54, 2012 Edition (National Fuel Gas Code), Section 7.13.2, CSST.

References

    This article is issued from Wikipedia - version of the 4/4/2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.